HMS - Anybus X-gateway IIoT-PROFIBUS DP-V0 Sla - AB7558

/ each
£754.00
Delivery
Essential specifications
Supply voltage DC - 24...24 V
Supporting protocol for TCP/IP - no
Supporting protocol for PROFIBUS - yes
Supporting protocol for MODBUS - no
Voltage type of supply voltage - DC
Packaging
1 each
GTIN
Supplier Ref
AB7558
Manufacturer Ref
AB7558
Commercial Reference
AB7558
Supply voltage DC:
24...24 V
Supporting protocol for TCP/IP:
no
Supporting protocol for PROFIBUS:
yes
Supporting protocol for MODBUS:
no
Voltage type of supply voltage:
DC
Supporting protocol for Data-Highway:
no
Supporting protocol for DeviceNet:
no
Supporting protocol for PROFINET IO:
yes
Supporting protocol for EtherNet/IP:
no
Supporting protocol for DeviceNet Safety:
no
Supporting protocol for other bus systems:
no
IO link master:
no
IP-rating:
IP20
Rail mounting possible:
yes
Wall mounting/direct mounting:
no
Front installation possible:
yes
Rack-assembly possible:
no
Width:
44 mm
Height:
127 mm
Depth:
114 mm
Anybus X-gateway IIoT – PROFIBUS Slave - OPC UA-MQTT
- Supports OPC UA micro-embedded profile
- Supports Discovery Services
- User name and password authentication
- Supports DataChange Subscription
- MQTT client acting as publisher
- Proven and tested with PLC’s from all leading manufacturers
- Possibility to build web pages to display and control a factory floor
- OPC UA
- Support for micro-embedded profile
- Supports Discovery Services
- Timestamp supported via discovery server
- User name and password authentication
- Supports DataChange Subscription
- Maximum 80 data point tags
- Dual port cut-through switch
- Dual RJ-45 ports available simultaneously
- MQTT
- MQTT client acting as publisher
- MQTT version 3.1.1 supported
- Json data encoding supported
- QoS 0-2 supported
- User name and password authentication
- Maximum 256 data point tags
- Dual port cut-through switch
- Dual RJ-45 ports available simultaneously
- PROFIBUS Slave interface
- PROFIBUS Slave settings can be made either via on-board switches, or by importing the provided .GSD file into engineering tool of the controlling PLC.
- Complete PROFIBUS-DP/DPV1 Slave functionality according to extensions of EN 50170
- Supports Class 1 & Class 2 services
- Automatic baudrate detection up to 12Mbit/s
- Max. Cyclic I/O data 244 bytes Input and 244 bytes Output, max 344 bytes total (in+out)
- Acyclic User Parameter data / Diagnostics length - up to 237 bytes
- Supports PROFIBUS features: Sync and Freeze and Watchdog
- PROFIBUS slave settings via on-board switches or vis .GSD file
- 1x D-sub 9-pin female PROFIBUS connector