Merlin Gerin - ACTI9 IC60N 2P 6A C MINIATURE CIRCUIT BR - A9F44206

/ each
£102.45
Delivery
Essential specifications
Release characteristic - C
Number of poles (total) - 2
Number of protected poles - 2
Rated current - 6 A
Built-in depth - 78.5 mm
Packaging
1 each
GTIN
Supplier Ref
A9F44206
Manufacturer Ref
A9F44206
Commercial Reference
A9F44206
Release characteristic:
C
Number of poles (total):
2
Number of protected poles:
2
Rated current:
6 A
Built-in depth:
78.5 mm
Rated voltage:
440 V
Voltage type:
AC
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V:
20 kA
Frequency:
50...60 Hz
Current limiting class:
3
Pollution degree:
3
IP-rating:
IP20
iC60N Circuit breaker, Curve C, 2P, 6A, 25/50kA, 12 to 440V, 50/60Hz, Circuit protection against short-circuit currents, Circuit protection against overload currents, Suitable for industrial isolation according to IEC/EN 60947-2 standard. Fault tripping indication by a red mechanical indicator in Circuit breaker front face
- With exclusive features, the Acti 9 iC60 DIN rail MCB is definitely geared to absolute safety and improved continuity of service.
- VisiSafe : for safe operation and maintenance work on circuits.
- Class-2 insulation : continuous safety for operators and unqualified personnel.
- VisiTrip : detects faulty Miniature Circuit-Breaker outgoers quickly and reduces intervention time.
- Add-on fully immune earth leakage protection devices : better continuity of service, especially in polluted environments and networks.
- Nominal current: 1 to 63 A
- Large choice of breaking capacities up to 100 kA and tripping curves: B, C, D, Compliance with standards IEC/EN 60898 or IEC/EN 60947-2,
- Full coordination with Acti 9 range Residual Current Devices (RCDs) and Compact NSX Moulded Case Circuit Breakers (MCCBs),
- Suitable for isolation in accordance with industrial standard IEC 60947
- Operating voltage: up to 440 V AC, insulation voltage: 500 V
- Optional add-on earth leakage modules: iC60 Vigi,
- Optional auxiliaries: indication of state and tripping, shunt tripping, undervoltage tripping, overvoltage tripping,
- The new reference in final distribution,
- Absolute safety of circuit protection with VisiSafe,
- Greater continuity of service with VisiTrip,
- Simple to choose with meaningful part numbers,
- Easy to install with quick, ergonomic & safe IP20B terminal shutters & robust connections (twice the standard tightening torque),
- Environmentally friendly with 100% recyclable & recoverable materials.
Merlin Gerin
Explore more products in this series