Essential specifications

  • Lightning impulse current (10/350) - 12.5 kA

  • Max. continuous voltage AC - 264 V

  • Mounting method - DIN rail (top hat rail) 35 mm

  • Construction size - 4 modular spacing

  • Nominal discharge surge current (8/20) - 50 kA

Packaging

  • 1 each

GTIN

4046356518550

Supplier Ref

2800183

Manufacturer Ref

2800183

Commercial Reference

2800183

Lightning impulse current (10/350):

12.5 kA

Max. continuous voltage AC:

264 V

Mounting method:

DIN rail (top hat rail) 35 mm

Construction size:

4 modular spacing

Nominal discharge surge current (8/20):

50 kA

Max. continuous voltage DC:

30 V

Nominal voltage AC:

240 V

Voltage protection level:

2 kV

Voltage protection level L-N:

1.2 kV

Voltage protection level N-PE:

1.7 kV

Follow current extinguishing capability:

0.1 kA

Max. conductor cross section solid (solid, stranded):

35 mm²

Max. conductor cross section flexible (fine-strand):

25 mm²

With remote signalling contact:

yes

Exhausting:

no

Signalling at the device:

Optic

Category type 1:

yes

Universal varistor-based plug-in lightning/surge arrester for 3-phase power supply networks with separate N and PE (5-conductor system: L1, L2, L3, N, PE), for Lightning Protection Levels III and IV, with remote indication contact


  • Plugs can be checked with CHECKMASTER
  • With floating remote indication contact
  • Secure hold of plugs in the event of high lightning current loads and strong vibrations thanks to new latching
  • Optical, mechanical status indication for the individual arresters
  • Pluggable
  • Thermal disconnect device for each individual plug
  • Mechanical coding of all slots