Prosoft - Modbus Serial Enhanced Communication Mod - MVI69E-MBS

/ each
£1,463.44
Delivery
Essential specifications
Number of HW-interfaces industrial Ethernet - 0
Number of HW-interfaces RS-232 - 2
Number of HW-interfaces RS-485 - 2
Supporting protocol for TCP/IP - no
Transmission rate - 115.2 kBit/s
Packaging
1 each
GTIN
Supplier Ref
MVI69E-MBS
Manufacturer Ref
MVI69E-MBS
Commercial Reference
MVI69E-MBS
Number of HW-interfaces industrial Ethernet:
0
Number of HW-interfaces RS-232:
2
Number of HW-interfaces RS-485:
2
Supporting protocol for TCP/IP:
no
Transmission rate:
115.2 kBit/s
Number of HW-interfaces PROFINET:
0
Number of HW-interfaces RS-422:
2
Number of HW-interfaces USB:
0
Number of HW-interfaces other:
1
Supporting protocol for PROFIBUS:
no
Supporting protocol for MODBUS:
yes
Supporting protocol for DeviceNet:
no
Supporting protocol for EtherNet/IP:
no
Supporting protocol for other bus systems:
no
Redundancy:
no
Explosion safety category for gas:
None
Explosion safety category for dust:
None
Width:
39 mm
Height:
131 mm
Depth:
87 mm
Compact I/O. Modbus serial enhanced communication module. 2 x serial ports
- Supports CompactLogix processors with 1769 I/O bus capability version 16 and greater (MicroLogix 1500 not supported)
- Add-on Instruction creates UDTs, providing logical definitions for I/O, status, and control data
- Add-on Profile support for RSLogix 5000, improving integration in the CompactLogix system
- Diagnostic data available in RSLogix 5000 controller tags, allowing decisions to be made based upon node health
- Module configuration backed up in CompactLogix project (ACD file)
- Module acts as a co-processor reducing impact to PLC scan time
- Supports up to 10,000 words of data
- Supports up to 250 Modbus Commands per port
- Each port can be configured individually as a Modbus Master or Modbus Slave device
- Supports Enron and Daniel-style Floating point data implementations
- Suitable for SCADA and field device interface applications
Prosoft