Weidmuller - VSPC 1CL 24VAC R - 8951560000

/ each
£103.37
Delivery
Essential specifications
Nominal voltage AC - 24...24 V
Nominal voltage DC - 34...34 V
Max. continuous voltage AC - 28 V
Max. continuous voltage DC - 40 V
Nominal discharge surge current (8/20) - 2.5 kA
Packaging
1 each
GTIN
4032248742806
Supplier Ref
8951560000
Manufacturer Ref
8951560000
Commercial Reference
8951560000
Nominal voltage AC:
24...24 V
Nominal voltage DC:
34...34 V
Max. continuous voltage AC:
28 V
Max. continuous voltage DC:
40 V
Nominal discharge surge current (8/20):
2.5 kA
Nominal load current:
0.45 A
Voltage protection level core/earth:
450 V
Voltage protection level core/signal ground:
450 V
Voltage protection level signal ground/protective ground:
650 V
Frequency:
2.6...2.6 MHz
Limiting frequency:
2.6 MHz
Mounting method:
On basic element
Connection 1:
Other
Pro-active thermo-control:
yes
With remote signalling contact:
no
Signalling at the device:
Optic
Explosion-tested version:
no
Surge voltage arrester (data networks/MCR-technology), with warning function / function indicator, analogue, Number of signals: 1, AC, 24 V, 34 V, 450
- Analogue signal/current loop (CL) protection includes the following signals:
- Signals from current loops (analogue measurements of sensors over long distances) 4 – 20 mA, 0 – 20 mA etc.
- Two-wire, three-wire and four-wire, without a common reference potential
- e.g. level indication signals from voltage sensors (analogue measurements of sensors over short distances) 0 – 10 V, PT 100 etc .; e.g. temperature measurement
- Pluggable arrester, with interruption-free and impedance-neutral plug-in and pull-out
- Can be tested with the V-TEST testing device
- Version with floating-earth PE connection used to avoid differences in potential
- Can be used in compliance with the IEC 62305 (D1, C1, C2 and C3) installation standard
- Integrated PE foot safely discharges up to 20 kA (8/20 μs) and 2.5 kA (10/350 μs) to the PE
- Colour coding of the voltage levels for fast identification on the panel
- Safety function through coding elements for different voltage levels
Weidmuller